HOME CONDOR PRODUCTS HUANLI PRODUCTS CUSTOM CONTROLS CONTACT US
> Pressure Transducers: EDI
> Pressue Sensor: EDS

> Electronic Control: EDR
> Electronic Control: EDRA

> Staging & Sequencing Control: GLW 4
> Staging & Sequencing Control: GLW 4-S

Download Complete Condor Catalog
(PDF Format)


Electronic pressure transducer with integrated relative pressure sensor for panel board mounting, quick-connect for plastic pneumatic tube. Analogue output 4 to 20 mA, operating voltage 12...30 V-DC.

Function:
The device converts the pressure applied to the sensor into a proportional DC- current (2 - wire technology).

Technical Data:
  • Measuring range: 0 - 2 bar, 0 - 10 bar, 0 - 16 bar
  • Max. perm. pressure: 3 bar bzw 25 bar respectively
  • Operating voltage: 12...30 V DC



  • DOWNLOADS:

    > EDI Condor Werke Catalog Pages


    Electronic pressure control with relative pressure sensor for direct installation either on or within a device. Thanks to the robust ceramic-sensor technology, the applied pressure is converted into a proportional DC-current signal (4 to 20 mA) in 2-wire technology. Electrical connection is effected in a straightforward and service-friendly manner - via a DIN 43650-A plug. In combination with this connection plug, the EDS type transducer also falls under the IP 65 Degree of protection class.

    Function:
    The device converts the pressure applied to the sensor into a proportional DC- current (2 - wire technology).

    Technical Data:
  • Measuring range: 0 - 6 bar, 0 - 10 bar, 0 - 16 bar
  • Current Output: 4...20 mA
  • Flange Connection: G 1/4"
  • Enclosure Protection: IP 65



  • DOWNLOADS:

    > EDS Condor Werke Catalog Pages


    Electronic pressure switch with integrated relative pressure sensor for panel board mounting, quick-connect for compressed air tube inlet, two fixed adjustable switching points, relay output (voltage-free change-over), analogue voltage output 0-10 V via jack plug (when ordering please indicate separately: order reference KL-S), operating voltage 230 V-AC, isolating transformer acc. to VDE 0550.

    Function:
    The device evaluates the applied pressure. On exceeding an upper threshold the relay is deactivated; when falling below a lower threshold the relay is activated again. Both thresholds are adjustable. The compressor is activated via terminals 11 and 14. In a current-free state, the relay is deactivated. Furthermore, and depending on the measuring range, the device provides an analogue output voltage of 0-10 V via jack plug.

    Technical Data:
  • Measuring range: 0,2 - 2 bar, 0,5 - 10 bar, 1 - 16 bar
  • Max. perm. pressure: 3 bar bzw 25 bar
  • Outputsignal: 0 - 10 V DC
  • Operating voltage: 230 V AC



  • DOWNLOADS:

    > EDR Condor Werke Catalog Pages


    Electronic pressure switch with integrated relative pressure sensor for panel board mounting, quick-connect for compressed air tube inlet, digital display for mains pressure indication and threshold programming (two switching points), relay output (voltage-free change-over), isolating transformer acc. to VDE 0550.

    Function:
    The device evaluates the applied pressure. On exceeding an upper threshold the relay is deactivated; when falling below a lower threshold the relay is activated again. Both thresholds also are adjustable without medium. The on/off thresholds can be programmed via the display during operation - the actual pressure status is shown on the display.

    Technical Data:
  • Measuring range: 0,2 - 2 bar, 0,5 - 10 bar, 1 - 16 bar
  • Max. perm. pressure: 3 bar bzw 25 bar
  • Operating voltage: 230 V AC



  • DOWNLOADS:

    > EDRA Condor Werke Catalog Pages


    Electronic staging and sequencing control for up to 4 compressors, quick connect for pneumatic plastic tube (internal pressure transducer, 1 to 16 bar) or connection of an external pressure transducer (not included; two-wire, 4 to 20 mA), 4 compressor inputs, 4 programmable, isolated SPDT's and one programmable, isolated alarm output, graphic display for programming and display of the system pressure, 3 keys for programming without having to connect to the air pressure system.

    Function:
    The staging and sequencing control GLW 4 detects the pressure and regulates even distribution of the compressor operating hours to all compressors installed in an air pressure system. The GLW 4 is the next generation of the very successful GLW 16. The GLW 4 can be adjusted without any special programming knowledge. Many additional application functions of the GLW 4 allow an even more specialized programming of the installation.

    Technical Data:
  • Measuring range (internal pressure transducer): 1 - 16 bar
  • Max. permissible pressure (internal pressure transducer): 25 bar
  • Operating voltage: 90 to 265 V-AC, 50/60 Hz
  • Enclosure dimensions: 140 x 90 x 59 mm
  • Mounting: 35 mm DIN rail according to EN 50022



  • DOWNLOADS:

    > GLW4 Condor Werke Catalog Pages


    GLW 4 in a plastic enclosure (Dimensions (LxWxH): 420 x 300 x 170 mm), mounted onto a DIN-rail, completely wired, with terminal blocks; terminal A1 features a 10A control voltage back up fuse;

    Optionally, an isolator and/or various rotary knobs and/or various indicator lights can be integrated and wired on to the front cover.

    Furthermore, it is also possible to feature the clients name and telephone number on the front label instead of the CONDOR LOGO.

    Delivery is carried out in individual packing including 3 mounted cable glands

    (M 20 x 1,5) and 3 loosely packed M 20 x 1,5 cable glands), GLW 4 Operating Manual, mounting and wiring instructions.



    DOWNLOADS: