Customer Support |
1-866-878-1497
Air Pressure Switch EDS Product detail
Pressure sensor EDS
Pressure range up to 16 bar
Output signal: 4 - 20 mA
Electronic pressure control with relative pressure sensor for direct installation
either on or within a device, G 1/4" connection, analogue output 4 - 20 mA and
operating voltage supply 11 - 30 V DC. Electrical connection is effected in a
straightforward and service-friendly manner - via a DIN 43650-A plug whereby a
degree of protection IP 65 is realized.
Function: the device converts the pressure applied to the sensor into a
proportional DC current (2 - wire technology).
|
|
| Part No. |
Order Reference | Measuring range(bar)* | Max. perm. pressure(bar) | Max. inaccuracy at 25° C | Operating voltage UB (V-DC)
|
| 260233 |
EDS 6 |
0 - 16 |
32 |
2,5% |
11 ... 30 |
| 260240 |
EDS 10 |
0 - 10 |
32 |
2,5% |
11 ... 30 |
| 260257 |
EDS 16 |
0 - 16 |
32 |
2,5% |
11 ... 30 |
|
*4 mA = 0 bar / 20 mA = measuring range end value.
|
|